American Type codex-mounted Transformer produci a Sina Manufacturing KEXUN est integrated et modularis parva distribution transformer, quae habet de compacta structuram, in urbana distribution et bonum tutela, et late in urbana distribution networks, residentialibus, commercial in locis et industrialis consumptio.
Model: Zbw-XII
Notam: Kexr

American TypePad-mounted Transformer habet sequuntur principalis features.

◆ Compact Design

Parvus minus area spatium apta loca limitata elit.

American box-genus TRANSFORMER structuram est adoptatur, quod plerumque installed in concreto codex-mounted.

◆ Pre-convenerunt structuram

Complete integrationem excelsum et humilis voltage virgas, transformers et tutela cogitationes antequam relinquens officinas ad redigendum in workload de-site installation.

Capere plene signatum structuram, humorem-probationem, pulvis-probationem et corrosio-probationem.

◆ salvus et reliable

Adopt ad redigendum periculum electrica inpulsa est plena periculum electrica.

Hoc est munera ONERO, brevi circuitu et temperatus tutela, et decurrit stabiliter.

◆ Erasile sustentacionem

American obturaculum-in cable capitis (cubito funem capitis) adoptatur, quod est convenient ad velox installation et postea. Consilio aditus ostium est rationabile et convenient ad operationem et sustentationem.

◆ fortis adaptability

American type codex-mounted transformator est idoneam ad velit amet, tutela gradu plerumque pervenit ip67.

Fusce consilio potest occursum diversis voltage levels (ut 10KV / 0.4kv) et facultatem requisita (ut 50kva ~ 1600kva). ◆


● Common Application missionibus American genus codex-mounted Transformer

✅urban Distribution Network: Conventum est potentia distribution mutatio platearum et Communitates, et reduces occupata regio.

✅residentialium regio: quietam consilio, idoneam virtutis copia residentialibus elit.

✅Commercial Centrum: Pulchra et pacto, sine afficiens civitatem specie.

✅INDustrial Park: Adapted dura environment cum princeps reliability.

✅Temporary Power consummatio: ut constructione sites, exhibitiones, etc., quod est convenient ad celeri instruere.


● Transformer Technical parametri usus per American genus codex-mounted Transformer

Vide

Item

Unitas

Technical parametri

1

Rated voltage

KV

X / 0.4

2

Max Operating voltage

KV

12

3

Rated frequency

HZ

50

4

Rated capacity

kva

15-1600

5

1min virtus frequency resistere voltage

KV

35

6

Fulgur impetus voltage

KV

75

7

Refrigerium


Onan

8

Fractio Current of High Voltage Tergum Fuse

in

50

9

Effrego current de plug-in Fuse

in

2.5

10

Temperature environment

-35 ~ XL

11

Liceat, coil temperatus ortu

65

12

Nulla-onus voltage ordinacione


± V% aut ± II * 2.5%

13

Sonitus campester

db

50

14

IP gradu


Ip43


◆ Summas comparationem damnum de diversis rerum Optimus

Capacity (KVA)

Voltage9 (KV)

Group connectens

Non-onus current%

Non onus damnum%

Imminedance voltage%

Lond damnum (W)

HV

LV

S9

S10

S1

S9

S10

S1

160





X ± V

Or2 * ± 2.5






0.4





Dyn11

Yyn0

1.4

1.4

0.2

400

320

255




4.0

2200

200

1.3

1.3

0.2

480

380

305

2600

250

1.2

1.2

0.2

560

450

360

3050

315

1.1

1.1

0.2

670

530

425

3650

400

1.0

1.0

0.15

800

650

505

4300

500

1.0

1.0

0.15

960

750

605

5100

630

0.9

0.9

0.15

1200

910

755

6200

800

0.8

0.8

0.15

1400

1080

980

4.5

7500

1000

0.7

0.7

1700

1260

10300

1250

0.6

0.6

1950

12000


◆ mensam technica parametri onus switch adoptavit

Item

Nomen

Unitas

315a

630a

Rated voltage


KV

12

12

Max current


A

315

630

Rated frequency


HZ

50

50

Rated Short-Circuit claudendo current


In

31.5

50

Rated brevi-term resistent current


In

12.5

50

Rated brevis-term resistent tempore


S

2

2

Mechanica vitae


Tempus

2000

2000

Fulgur impetus test

Ad terram



KV

75

75

SECUNDUS Fractura

85

85

1min laboris frequency resistere voltage

Ad terram

42

42

SECUNDUS Fractura

48

48

Rated Peak resistite current


In

31.5

50


◆ Type of American Type Pad-mounted Transformer

American Type Pad Mounted Transformer

ZBW-XII Pre-installed American arca archa type substation vexillum dimensiones

Capacity (KVA)

A

B

C

D

E

F

H

C ~ CCL

1900

1650

1250

650/800

600

1410/1560

1450

315

1900

1650

1350

650/800

650

1460/1610

1450

CD ~ D

1900

1750

1450

650/800

650

1490/1640

1550

630

1900

1750

1550

650/800

700

1580/1730

1550

800

1900

1850

1550

650/800

700

1640/1790

1650

1000

1900

1850

1650

650/800

700

1640/1790

1650



Hot Tags: American genus codex-mounted Transformer
Mitte Inquisitionem
Contactus info
Nam inquiries de funem genere arca archa, princeps voltage switchgear, humilis voltage switchgear et pretium album, placere relinquere vestri email ad nos et in tactus in XXIV horas.
X
We use cookies to offer you a better browsing experience, analyze site traffic and personalize content. By using this site, you agree to our use of cookies. Privacy Policy
Reject Accept